Before 3pm on a working day, contacted the same day. After 3pm, the next working day. Contact, not a quotation. Telephone
Start a project brief
Soft cream open-cell spray foam filling the bays between timber studs, its surface textured like an acoustic panel, in soft daylight.

Systems and specification

Open-cell spray foam: for hybrid systems, sound, and build-ups that breathe.

A light, flexible foam whose cells are open to each other. It absorbs sound, lets water vapour pass, and costs less per millimetre than closed-cell. HOLVEM uses it in hybrid systems with closed-cell foam, where sound absorption is needed, and where the build-up has to stay breathable. Not directly on a cold metal sheet.

  • Best in hybrid systems
  • Acoustic absorption
  • Vapour-open, breathable build-ups

01What open-cell foam is

Open cells, and everything that follows from them.

The same two-component chemistry as closed-cell, blown with water so the cells burst open as the foam expands. Air fills them instead of a sealed gas, and every difference between the two systems comes from that.

01 · Soft

Light, flexible, easy to trim.

Open cells make a low-density foam that gives under a thumb, moves with timber as it dries and shrinks, and is trimmed flush with a saw or a blade. It expands many times more than closed-cell as it is sprayed, so it fills deep voids quickly.

02 · Vapour-open

Moisture passes through it.

Water vapour moves through the open cells almost as freely as through air. The build-up has to be able to dry, and in most UK assemblies that means a vapour control layer on the warm side and a surface on the cold side that can shed what gets through. It is never itself the vapour barrier.

03 · Acoustic

It absorbs airborne sound.

The open structure that lets vapour through also traps sound. Sprayed into a ceiling void, a partition or under a floor it reduces the sound passing through, which closed-cell foam, being rigid and sealed, does very little of.

04 · Per millimetre

Lower cost, higher λ.

λ about 0.038W/mK · OPEN-CELL · CONVERTED FROM THE US DATA SHEET

Air conducts heat better than the gas in a closed cell, so open-cell foam has a higher thermal conductivity and needs more depth for the same resistance. Its price per millimetre is lower; its price per unit of resistance is the comparison that matters, and depends on the void being filled.

02Why not on a cold sheet

On a metal roof, the vapour has to be stopped before the steel.

A profiled metal sheet is the coldest surface in the building on a winter morning, and the room below it is full of moist air. Whatever is sprayed on the sheet either stops the vapour at its face or lets it through to the steel. That is the whole difference, drawn.

Room vapour passes through the open cells to the sheet, which is below the dew point. It condenses there, inside the foam, against the steel.

Section, not to scaleThe same sheet, the same room air, on the same cold morning.

03On commercial buildings

Three places open-cell earns its keep, and one where it does not.

Open-cell foam is usually best in a hybrid system with closed-cell foam, where sound absorption is needed, or where the build-up has to stay breathable. The condensation risk analysis says whether a vapour-open layer belongs, and it is run before either system is specified.

01Hybrid systems

Inside a closed-cell layer, as the second insulation.

The build-up HOLVEM reaches for most often. Closed-cell does the vapour and air-sealing work against the cold face; open-cell fills the depth behind it.

  • A closed-cell layer on the sheet or deck first, stopping the room's vapour at a face that stays above the dew point and sealing every lap and fixing.
  • Open-cell inside it, to the depth the U-value target sets, at a lower cost per millimetre than carrying the whole depth in closed-cell foam.
  • The condensation risk analysis sets the split: enough closed-cell depth that the interface between the two foams stays warm and dry.
How the analysis sets the closed-cell depth in a hybrid

02Sound absorption

Where sound absorption is the objective.

The open structure that lets vapour through also traps airborne sound. Closed-cell foam, rigid and sealed, does very little of this.

  • Ceilings, soffits and partitions in offices, studios and mixed-use buildings, where the brief asks for a quieter room, not only a warmer one.
  • Rain noise on lightweight roofs, where an open-cell layer inside the closed-cell layer takes the edge off the drumming.
  • Under floors and in voids between occupied spaces, reducing the sound passing through the structure.

03Breathable build-ups

Where the assembly has to stay vapour-open.

Some build-ups are designed to dry outwards through the insulation. A vapour-resistant foam there would trap moisture; an open-cell layer lets it move.

  • Timber-framed roofs and walls with a vapour control layer on the warm side, where the analysis shows the assembly drying every year.
  • Deep timber voids and irregular cavities, which the foam's expansion fills completely at a lower cost per millimetre than a rigid foam.
  • Behind an existing vapour control layer, where a second vapour-resistant layer would trap the first between two closed faces.

04Not here

Not directly on a cold metal sheet.

The sheet sits below the dew point and open cells carry the room's vapour straight to it. The condensation moves into the foam; it does not stop.

  • The underside of profiled metal roofs and walls: closed-cell's vapour resistance is what protects the steel, and it is what HOLVEM specifies there.
  • Fibre-cement and asbestos-cement encapsulation, which needs a rigid, bonded, vapour-resistant layer that stiffens the sheet.
  • Anywhere the layer must seal laps and fixings or add stiffness. A soft, open foam cannot do either.
Closed-cell system data: Enverge NexSeal LE

04System data

Open-cell beside closed-cell.

The manufacturer's figures for the open-cell system HOLVEM applies, beside the closed-cell system's, so the two can be read together. Each figure is the manufacturer's, the test house's or the certifying body's, and is quoted as such; values converted from US units are marked.

PropertyOpen-cell: SucraSealClosed-cell: NexSeal LE
ProductEnverge SucraSealEnverge NexSeal LE
Cell structureOpen-cell; air-filledClosed-cell; over 90 per cent closed cells (ASTM D6226)
Thermal conductivity, λ0.039 W/mK below 100 mm and 0.040 W/mK at 100 to 200 mm, declared values in the BBA certificate (23/6845); the manufacturer’s US data sheet converts to about 0.0380.027 W/mK declared by the manufacturer to BS EN 14315-1
Density, as applied12 to 24 kg/m³ to BS EN 1602 (BBA 23/6845); the manufacturer’s data sheet gives about 8 kg/m³ nominal by the US method (ASTM D1622)35 to 47 kg/m³ to BS EN 1602 (BBA 23/6963)
Water vapour resistance factor, μAbout 7, converted from the manufacturer's US permeance figure (ASTM E96); vapour-open62 to BS EN 12086, declared by the manufacturer; vapour-resistant
Sound absorptionIn laboratory tests to BS EN ISO 10140 on a blockwork wall, 150 to 300 mm improved the sound reduction index by about 3 to 5 dB, mainly at mid and high frequenciesDISTRIBUTOR DATA · NO LABORATORY OR REPORT NUMBER GIVENNot a property claimed for the system
Reaction to fireClass 1 surface spread of flame to BS 476-7:1997, uncoated, tested at 50 mm nominal on 9 mm plywood (Warringtonfire report 508786, 25 October 2021). BS 476-7 is a British surface-spread-of-flame test, not a Euroclass; no Euroclass is held for the open-cell systemCoated with DC315: Euroclass B-s2,d0 to BS EN 13501-1:2018 as tested, 35 to 40 mm of NexSeal LE on 9 mm plasterboard with DC315 at 0.7 mm wet film thickness (BTTG report 27/06638/12/24); the classification applies to the build-up tested and is confirmed for each project against the fire strategy. Uncoated: Class 1 surface spread of flame to BS 476-7 (BTTG 27/06605/10/24), not a Euroclass
BBA certificateAgrément Certificate 23/6845, Product Sheet 1, pitched roofs (as ThermoFoam Sucraseal 0.5); domestic buildingsAgrément Certificate 23/6963, Product Sheets 1 to 3: pitched roofs, external walls, suspended timber floors (as ThermoFoam Nexseal 2.0); domestic buildings
RatePriced per projectRates in the cost guide, foam only. The coated Euroclass B system is priced separately.

Your next step

Your building.
Your brief.
A specialist.

You do not need to choose a system. Tell us what the building is and what the roof or wall is doing; the system follows from the build-up and the analysis, and someone who does this every day comes back to you.

Start a project brief About five minutes. Photographs help; nothing else is needed.

Already have drawings or a specification?

Send them for technical review. Drawings, a written specification or a calculation are checked against the roof as it will be built, the bridge included. A review, not a quotation.

Upload for technical review