Worked example
A metal standing-seam flat roof, South East England
- Foam
- 50 mm NexSeal LE between timbers: R 1.85 on its own; 1.56 once the timber at five per cent of the area is included
- Wool
- 250 mm mineral wool between joists: 5.39 with the timber included
- Rest
- Surfaces, air layer, deck and board: 0.41
- Total
- RT 7.41 m²K/W: the layers sum to the lower limit, 7.35; the combined method averages it with the upper limit, 7.46. Air-gap correction 0.0053 W/m²K.
U 0.14 W/m²K. The clear path between the timbers alone would give 0.12; the timber pulls the roof to 0.14. Here the foam layer did the condensation and airtightness work against the deck, and the mineral wool did most of the thermal work. Double the foam and the roof's U-value moves a little; ignore the timber and the figure is wrong.
The full calculation, step by step